Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2004 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :*/1)SOIL WATER TEST IS OK 2)HCS CONNECTION IS OK 3)OK TO BACKFILL TRENCH | |
| 11/15/2004 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection :*/HAVE PLAN AND PERMIT ON SITE AT TIME OF INSPECTION | |
| 11/12/2004 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)PROVIDE MINIMUM 1/8" PER FOOT FALL ON BUILDING SEWER. 2)PROVIDE FULL SIZE UPPER TERMINAL CLEANOUT ON BUILDING SEWER |