Permit: T04CM04199

Parcel: 10925013B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
03/24/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
03/23/2005 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :* 1) WHERE ARE OUTLETS FOR CIRCUIT 23, 25, 27, 29 2) WHERE IS WILDAN APPROVAL STAMP?
12/23/2004 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) WHERE IS DISCONNECTING MEANS FOR ROOM A/C UNIT
2) SUPPORT FLEX CONDUIT AS PER CODE (SWITCHES/NEW LIGHT FIXTURE
3) ATTACH FIXTURE TO GRID
4) INSTALL OFFICE FURNITURE TO CHECK CONNECTIONS
5) GROUNDING EQUIPMENT CONDUCTORS TO A/C'S TO BE AS PER 250.1220
6) A/C CIRCUITS NOT AS PER PLANS
12/03/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) THERMOSTAT WIRE TO BE SUPPORTED AS PER 725.6
2) FINISH ENTRY HALL
3) MISSING LIGHT FIXTURE