Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 07/28/2005 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Approved |
IVRS - Inspection :* |
| 05/18/2005 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Partial Approval |
IVRS - Inspection :* 1) ENGINEER @ TURNER ENGINEER (JIM) WILL PROVIDE FIX FOR INSUFFICIENT LAP LENGTH( APPROVED ON PLAN BUT DOES NOT MEET ACI 318 CHAPTER 12 REQS) I MET WITH HIM YESTERDAY AND HE SAID HE THOUGHT 24" LAP WOULD WORK BUT i NEED CONFIRMATION IN WRTINTING. NEW CALCS FROM ENGINEER DONE USING 40 KSI STELL. CURRENT LAP LENGHTS OK RFI TO BE FILED WITH PLANS. |
| 05/17/2005 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Not ready for Inspection |
IVRS - Inspection :* YOU NEED TO CHAIR COLUMN STEEL. GSN FOR LAP DEVELOPMENT OF DEFORMED BAR IN CONCRETE DO NOT APPEAR CORRECT. GSN 111.9 PP SI.1 GRADE 60 #5 BAR. ACI 318-36? |
| 05/04/2005 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Partial Approval |
IVRS - Inspection :* COL FOOTINGS FOR CANOPY LINE 1 & LINE 2 |