Inspection Status: Approved
Inspection History: ROOF NAILING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/28/2005 |
ROOF NAILING |
|
Approved |
IVRS - Inspection :* |
| 02/23/2005 |
ROOF NAILING |
|
Partial Approval |
IVRS - Inspection :* 1) HINGE BRACING 2ND FLR ROOF REAR GABLE WOOD SPLIT, SOME NOT NAILED 2) NEED WIND BRACE REAR WALL 3) 2ND FLR. FRONT BEDROOM EAST BELOW WINDOW ( SHEATHING) NOT NAILED UNDER 2 X4 FOR FLASHING 40 HUS26 HANGER AT SMALL GIRDER 2ND FL REQS 16 COMMON NAILS. 5) MISSED LEDGER AT SMALL SHED ROOF GARAGE, NEED A TIE FOR ROOF TO WALL. 6) X BRACE TRUSSES EA END. 7) CAN'T FIND DETAIL SHOWING 3 1/8" X 12" ?? SPANING CLEAR TO EDGE OF ??. 8) O.S.B TURNED PARALELL TO TRUSSES FRONT ROOF 2ND FLOOR, BLK JOINTS 9) NEED TRUSS DRAWINGS. 10) REAR PORCH POST/BEAMS HARDWARE REQS 16D. |