Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2004 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 09/27/2004 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SECURE GAS LINE AT H20 HEATER 2) INSTALL TYPE B VENT HEATER 3) INSTALL NEW PRESSURE/TEMP RELIEF VALVE AND LINE TO EXTERIOR OF CABINET 4) MUST HAVE SHUT OFF VALVE BEFORE UNION ON ROOF 5) MUST SUPPORT GAS PIPING ON ROOF MAXIMUM 6' SPACING 6) COMPLETE ALL ABOVE 7) RETEST AND RECALL FOR 03050 AGAIN |
|
| 09/24/2004 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NO PRESSURE TEST ON GAS LINE. MUST HAVE MINIMUM OF 10 PSI PRESSURE ON LINE AT TIME OF TEST |