Permit: T04CM04122

Parcel: 140375770


Addresses:

5961 E CEDARBIRD DR

Inspection Status: Approved

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
01/28/2005 ROOF NAILING Approved IVRS - Inspection :*
AP
01/26/2005 ROOF NAILING Denied IVRS - Inspection :
There is no plan or job inspection card on site.| 925*
01/19/2005 ROOF NAILING Partial Approval IVRS - Inspection :*
1) OK TO LOAD (ROOF)
01/11/2005 ROOF NAILING Not ready for Inspection IVRS - Inspection :*
1) LEAVE COPY OF TRUSS DRAWINGS ON SITE
2) SHIM ALL 3 PT BEARING TRUSSES (FULL BEARING)
3) USE 16D COMMON NAILS IN TRUSS TO GIRDER CONNECTION HUS26 HANGERS, 10D TECO'S GOOP FOR 54 PERCENT LEAD CARRIED
4) SHEAR PANELS BUILT BETWEEN TRUSSES GARAGE SHEAR TRANSFER
5) CONCRETE REPAIR, NEED ENGINEERED DETAIL STAMPED BY ENGINEER OF RECORD
6) MISSING TWO SD DETAIL PAGES IN THIS PLAN SET
12/16/2004 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SOUTH WEST CORNER OF SLAB, CABLE HAS FAILED PROVIDE ENGINEERING REPAIR AND APPROVED BY CITY OF TUCSON
2) DO NOT LOAD ROOF UNTIL SLAB REPAIR IS DONE
3) CHECK ALL OVERFRAMING AND EDGE NAILING
12/13/2004 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO SHEARWALL PLANS
2) NO TRUSS DRAWINGS
3) NO LADDER
4) 2ND REJECTION REFEE DUE
12/10/2004 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE ACCESS TO ROOF