Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T04CM04120

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
11/19/2004 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
11/15/2004 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) HOLDOWN ON WEST WALL SOUTH PANEL NORTH END NOT INSTALLED ON ?
2) FLATENING H2.5 CLIPS NOT ALLOWED AT GARAGE WEST WALL
3) DRYWALL SHEAR WALLS INSTERSECTED BY INTERIOR WALLS CANNOT BE CONNECTED BY LADDER BACKING. PROVIDE AN ENGINEERS APPROVED DETAIL FOR SHEAR TRANSFER AT INSTERSECTING WALLS
4) HOUSE ROOF OK TO DRY IN
5) PORCH ROOF NOT NAILED