Permit: T04CM04106

Parcel: 12604043E


Addresses:

4454 E 3RD ST #01


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T04CM04106

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/23/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/17/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) CONDENSATE LINES-WHERE ARE TRAPS
2) APT #1 INSULATE SUCTION LINE AT A/H
3) BOTH APTS CONDENSORS AND A/H DIFFICULT TO REMOVE BLOCK AT FUSED SWITCH. NEED TO BE ADJUSTED
4) CONDENSING UNIT ON APT #1 GOING TO BE RELOCATED TO MAINTAIN CLEARANCE AT ENTRANCE SERVICE ??