Inspection History: ELECTRIC - FINAL

Permit Number - T04CM04106

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/25/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK FINAL
08/23/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ONLY ONE CONDUCTOR TO A GROUND SCREW
2) SHARED NEUTRAL ON ARC FAULT MAY CAUSE TRIPING
3) MAINTAIN CLEARANCE A/C DISCONNECT #2
4) TIGHTING ALL LOOSE FITTINGS
5) FINISH PREVIOUS ITEMS #4, 5, 6, 8 AND 10
08/17/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE #2
2) PROPERLY INSTALL CONDUIT TO IRRIGATION BOX
3) CORRECTLY SIZE BREAKER TO CONDUCTOR AMPICITY 334.80
4) CORRECTLY IDENTIFY UNDERGROUNDED CONDUCTORS A/C'S
5) RECEPTACLE COVERS TO BE WEATHER PROOF WEATHER OR NOT PLUGED INTO 406.8
6) TIGHTEN LOOSE WATER HEATER FITTINGS AND A DISCONNECTING MEANS IS NEEDED
7) BATH FIXTURE TO BE MOUNTED OVER BOX AND GROUNDED
8) AN APPROVED CONNECTOR IS NEEDED AT HOOD
9) 2 CIRCUITS TO SERVE COUNTER TOPS 210.52
10) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RINS 314.20