Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM04106
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 08/23/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ONLY ONE CONDUCTOR TO A GROUND SCREW 2) SHARED NEUTRAL ON ARC FAULT MAY CAUSE TRIPING 3) MAINTAIN CLEARANCE A/C DISCONNECT #2 4) TIGHTING ALL LOOSE FITTINGS 5) FINISH PREVIOUS ITEMS #4, 5, 6, 8 AND 10 |
|
| 08/17/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE #2 2) PROPERLY INSTALL CONDUIT TO IRRIGATION BOX 3) CORRECTLY SIZE BREAKER TO CONDUCTOR AMPICITY 334.80 4) CORRECTLY IDENTIFY UNDERGROUNDED CONDUCTORS A/C'S 5) RECEPTACLE COVERS TO BE WEATHER PROOF WEATHER OR NOT PLUGED INTO 406.8 6) TIGHTEN LOOSE WATER HEATER FITTINGS AND A DISCONNECTING MEANS IS NEEDED 7) BATH FIXTURE TO BE MOUNTED OVER BOX AND GROUNDED 8) AN APPROVED CONNECTOR IS NEEDED AT HOOD 9) 2 CIRCUITS TO SERVE COUNTER TOPS 210.52 10) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RINS 314.20 |