Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2005 | MECHANICAL - FINAL | Approved | ||
| 02/03/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* RELOCATE TRAP ON WALK IN COOLER FAN COIL. CONNECT DRAIN TO EVAP COOLER. USE A BUSHING WHERE ELEC. CONDUIT PENETRATE HOUSING ON MAKE UP AIR UNIT. MOUNT GREASE BOX TO EXHAUST FAN. LABEL A/C UNITS W/SUITE NUMBER. PROVIDE FRESH AIR INTAKES. PROVIDE FLUE VENT CAP ON UNITS. A/C 3 OVERFUSED. |
|
| 01/31/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* OK FOR GAS CARD |