Permit: T04CM04068

Parcel: 122060260


Addresses:

4311 E LINDEN ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T04CM04068

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/29/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/26/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) MAINTAIN CLEARANCE IN FRONT OF A/C DISCONNECT-GAS PIPING
2) GROUNDING ELECTRODE CONDUCTOR IN METAL CONDUIT TO BE BONDED TO RACEWAY 250.64
3) FINISH EXTENDER RINGS
08/23/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) FINISH PREVIOUS ITEMS
08/14/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) APPROVED BONDING DEVICES AT CONCENTRICS OF TRANSFORMER CHASE NIPPLES NOT APPROVED 250.97, 110.3
2) ONLY ONE CONDUCTOR PER TERMINAL 110.3 AND 110.14
3) BOND CONTRACTOR BOX
4) FILL UNUSED OPENINGS IN GUTTER AND USE A BOND BUSHING ACCROOS CUT CONCENTRICS 250.97
5) TIGHTEN LOOSE FITTINGS
6) APPROVED EXTENDER RING ARE NEEDED FOR BOXES MORE THAN 1/4" IN NON COMBUSTIBLES 314.2-METAL NOT APPROVED
7) LABEL MAIN DISCONNECT SWITCH
8) PLEASE VERIFY INSPECTION FOR RECESSED CANS
08/11/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) POWER HAS BEEN ENERGIZED WITHOUT CLEARANCES. PLEASE HAVE ELECTRICAL PRESENT TO OPEN ELECTRICAL EQUIPMENT
2) MAINTAIN DEDICATED SPACE ABOVE PANEL
3) EM CANS NOT WORKING
05/24/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK RESTROOMS, JANITORS CLOSET, ELECTRIC ROOM, WALLS AND HARD LIDS
05/05/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/01/2005 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled