Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/23/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) LOCKED-NO ACCESS |
|
| 08/11/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/10/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) COMPLETE PREVIOUS ITEMS #2 DATED 5/26/05 2) BOTH EM CANS NOT WORKING 3) PLEASE HAVE ELECTRICIAN PRESENT TO PROVIDE ACCESS TO NEW RUN |
|
| 08/03/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) A BOND BUSING IS NEEDED FOR CONCENTRICS OVER 250V AND SECONDARY SIDE OF TRANSFORMER 2) A BONDING JUMPER (MAIN) IS NEEDED TO GROUNDED CONDUCTOR 3) IDENTIFY PHASE CONDUCTORS 4) MISSING LOCK NUT PANEL "MP-L" 5) NORTH EM CAN LIGHT NOT WORKING 6) PLEASE PROVIDE ACCESS TO CHECK FEEDER CONNECTIONS AT MAIN BLDG 7) POWER HAS NOT BEEN AUTHORIZED TO ENERGIZE. PLEASE COMPLETE ITEDMS 1-3 AND 6 TO ENERGIZE |
|
| 05/26/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) JUNCTION BOXES TO BE ACCESSIBLE 2) MAINTAIN DEDICATED AREA ABOVE PANELS 3) MAINTAIN 6' SEPERATION CLASS "A" FIRE ALARM SYSTEM 4) OK HALL CEILING 5) OK OUTSIDE SOFFITS-8 CANS |
|
| 04/26/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/21/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |