Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T04CM04066
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/11/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* CLOSET FLANGES ARE OK | |
06/21/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PIPE IS TO BE CUT OFF FLUSH WITH THE TOP OF THE CLOSET FLANGE. IF YOU ARE USING A COMPRESSION FLAGE IT IS IMPORTANT TO HAVE IT INSTALLED IN PRACTICAL ALIGNMENT. | |
05/03/2005 | PLUMBING - INTERMEDIATE | Partial Approval | 1) GAS PRESSURE TEST IS OK. 2) OVERHEAD WATER DISTRIBUTION IS OK. 3) SOIL WATER TEST FOR DWV SYSTEM. 4) NOTE: SHALL SEE CLOSET FLANGE INSTALLATION PRIOR TO SETTING WATER CLOSETS. | |
04/26/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 3/4" YARD WATER LINE FOR H.B SUPPLY IS OK. 2) OK TO BACKFILL TRENCH |