Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/24/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection :INSTALL GFCI OUTLET IN BATHROOM PER PLAN INSTALL OUTLETS ON EAST AND SOUTH WALLS OF PLAY ROOM PER PLAN INSTALL SWITCH TO EXTERIOR LIGHT FRONT EXTERIOR DOOR RAISE SMOKE DETECTOR 6-12" FROM CEILING MAIN SERVICE PANEL ALL BREAKERS MUST BE IN TOP PANEL. COVER BLANK SLOTS IN PANEL |
|
| 11/23/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |