Permit: T04CM04048

Parcel: 13110034A


Addresses:

5500 E 22ND ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T04CM04048

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/22/2005 MECHANICAL - FINAL Approved IVRS - Inspection :* ALL CORRECTIONS HAVE BEEN MADE OK FOR FINAL C OF O. LEFT GAS CARD
02/18/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :* PROVIDE SUPPORT ON DRYER VENTS. PROVIDE SCREENS TO KEEP BIRDS OFF OF COMBUSTION AIR SCREEN
02/15/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* DRYER VENTS MUST HAVE A MIN 2" CLEARANCE FROM COMBUSTIBLES. ALL CONNECTORS ON DRYER VENTS MUST RUN THE SAME DIRECTION OF THE AIRFLOW. PROVIDE THE LISTING ON THE TAPE USED FOR DRYER VENTS. ADEQUATELY SUPPORT DRYER VENTS WITH METAL SUPPORT BRACKETS AS PER PLANS. PROVIDE ADEQUATE CLEARANCE AROUND WATER HEATER VENT. PIDGEONS ARE NESTING ON TOP OF COMBUSTION AIR VENT SCREEENS. RELOCATE SCREENS TO KEEP BIRDS FROM BLOCKING AIR FLOW. PROVIDE WATER, ELECTRICAL CONNECTIONS & DRAINS ON EVAP COOLER. SCHEDULE MECH. INTERMEDIATE & MECH ABOVE CEILING INSPECTIONS.