Permit: T04CM04048

Parcel: 13110034A


Addresses:

5500 E 22ND ST


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T04CM04048

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
01/26/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :* PERM CAPS INSTALLED OK APPROVED
12/17/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)WRAP PIPE SO THAT NO PIPING IS DIRECTLY IMBODDED IN CONCRETE. 2)PROVIDE PERMANENT CAP FOR ANY PIPING REQUIRING CAPPING BELOW GRADE. (AT MOP SINK) PRIOR TO COVERING WITH CONCRETE. SEE NOTE 1 FROM 12/9/04
12/09/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/WATER TEST ON CONTINUATION OF 6" BLD DRAIN AND 6" BLD SEWER TO POINT OF CONNECTION AT MAIN OK 1)CALL IN FOR INSPECTION PRIOR TO CONCRETE POUR FOR PIPE WRAPS & FLOOR DRAINS AND VIEWING ON ANY DEMO PLUMBING 2)HAVE YOUR YELLOW PERMIT CARD ON SITE OR NO MORE INSPECTIONS
11/03/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/TRAP ARMS OK FOR INTERIOR CONCRETE. 1)NEED TO VIEW CONTINUATION OF BUILDING DRAIN THRU 2-WAY CLEANOUT TO POINT OF CONNECTION TO SITE SEWER HCS. 2)POST YOUR YELLOW PERMIT CARD ON THIS SITE.
11/02/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/WATER TEST WASTE & VENT UNDERGROUND TO EDGE OF REAR DOOR OK EXCEPT NEED RETEST ON 2" FLOOR DRAINS REQUIRE 2X'S PIPE DIAMETER BETWEEN SANTEE AND P-TRAP