Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2006 | PLUMBING - FINAL | Approved | OK TO COVER YARDWATER PLUMBING FINAL OK OK FOR C OF O S.T.O.I |
|
| 09/06/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PVC YARDWATER CONNECTIONS AT METERS COVERED BEFORE APPROVAL. |
|
| 09/05/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE REREAD THE LAST LINE FROM NOTES 08/31/06 YOU ARE REQUIRED TO HAVE 12" OF COVER AT THE METER. WHERE YOU HAVE MADE A SWING JOINT UP AT THE METERS YOU CAN'T POSSIBLY HAVE 12" OF COVER. |
|
| 08/31/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE CALL IN AND HAVE APPROVED ALL REQ'D INSPECTIONS, PRIOR TO CALLING FINAL. 2. PLUMBER EXPLAINED THAT YARDWATER PIPING WAS INSTALLED IN 2005 AND EXEMPT FROM TRACER REQUIREMENTS, HOWEVER PVC YARDWATER PIPING REQUIRES 12" OF COVER AT ALL POINTS, ESPECIALLY WHERE YOU MADE A SWING JOINT UP AT METER CONNECTIONS. |