Permit: T04CM04046

Parcel: 113071220

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
02/07/2006 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*BOND SERVICE RISER WITH CLAMP OR CHANGE TO LOCKNUTS AND BUSHING. IDENTIFY NEUTRALS @ DISPOSAL AS HOT, FIRE CAULK UPSTAIRS
02/03/2006 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
The service is not per code.| 210*
1. MAKE CORRECTIONS #3 AND #4 FROM PREVIOUS INSPECTION
02/01/2006 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CORRECTLY IDENTIFY HOUSE PANEL
2. DRIVE GROUND RODS FLUSH
3. SQUARE UP AND BOND SERVICE RISER (LOCKNUTS AND GROUNDING BUSHING)
4. PROVIDE EQUIPMENT GROUND AND GROUND TERMINAL FOR HOUSE PANEL.
5. MAKE UP FEEDERS
6. REMOVE BONDING JUMPER (NEUTRAL BONDED TO CAN ALREADY)
7. HAVE EQUIPMENT OPEN FOR NEXT INSPECTION.