Permit: T04CM04045

Parcel: 113071220

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/08/2006 PLUMBING - FINAL Approved 1. OK TO COVER YARDWATER
2. PLUMBING FINAL OK
3. OK FOR C OF O S.T.O.I
09/06/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CONNECTIONS AT METER COVERED BEFORE APPROVAL
09/05/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
ALL OF THE YARDWATER PIPING NEEDS TO BE CONNECTED
ALL OF THE YARDWATER PIPING REQUIRES AT LEAST 12" OF COVER -- THIS INCLUDES THE PIPING AT THE METERS
08/31/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
DO NOT POUR SIDEWALK!!!
PVC YARDWATER REQUIRES 12" OF COVER AT ALL POINTS.
CALL 03040 AND HAVE THIS TAKEN CARE OF BEFORE YOU CALL FINAL.
08/24/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. BLDG. NUMBERS NOT POSTED
2. PVC REQUIRES A MINIMUM OF 12" OF COVER AT ALL PTS.
3. WHERE ARE YOUR TRACER WIRES FOR PVC WATER PIPING?