Permit: T04CM04045

Parcel: 113071220

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/30/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1101 -- BURIED CHIME
1102 -- WATER HEATER LOCKOUT
1103 -- DEAD KITCHEN RECEPTACLES
1104 -- MASTER/SMOKE DETECTOR TO CLOSE TO SIDE WALL?
AND 2ND BEDROOM
1105 -- MASTER SMOKE TO CLOSE TO WALL?
08/23/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR INTERIOR OF UNIT 1101 ONLY -- CHECK ALL UNITS FOR THESE CORRECTIONS BEFORE CALLING FOR NEXT FINAL.
1. ONLY ONE NEUTRAL UNDER SAME SCREW IS ALLOWED IN SUBPANEL -- NEC 408.21
2. ONLY THE SAME SIZE EQUIPMENT GROUNDS CAN BE UNDER SAME SCREW IN SUB-PANEL (NEC 110.3 (B) AND 110.14)
3. THE PANEL DIRECTORY IS INCORRECTLY IDENTIFIED -
NEC 408.4
4. PROVIDE A DISCONNECTING MEANS FOR WATER HEATER
NEC 422.31 (B)
5. ALL OUTLETS IN BEDROOMS REQUIRE ARC FAULT PROTECTION INCLUDING LIGHTS, RECEPTACLES AND SMOKE DETECTORS - NEC 210.12
6. TIGHTEN ALL RECEPTACLES SO THEY ARE NOT LOOSE IN WALL -- NEC 406.4
7. COUNTER GFI BLOCKED BY REFER - NEC 210.52(C)(5)
8. MAKE SURE SMOKE DET. ARE MOUNTED PER THEIR INSTRUCTIONS -- NEC 110.3