Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1101 -- BURIED CHIME 1102 -- WATER HEATER LOCKOUT 1103 -- DEAD KITCHEN RECEPTACLES 1104 -- MASTER/SMOKE DETECTOR TO CLOSE TO SIDE WALL? AND 2ND BEDROOM 1105 -- MASTER SMOKE TO CLOSE TO WALL? |
|
| 08/23/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* INSPECTION FOR INTERIOR OF UNIT 1101 ONLY -- CHECK ALL UNITS FOR THESE CORRECTIONS BEFORE CALLING FOR NEXT FINAL. 1. ONLY ONE NEUTRAL UNDER SAME SCREW IS ALLOWED IN SUBPANEL -- NEC 408.21 2. ONLY THE SAME SIZE EQUIPMENT GROUNDS CAN BE UNDER SAME SCREW IN SUB-PANEL (NEC 110.3 (B) AND 110.14) 3. THE PANEL DIRECTORY IS INCORRECTLY IDENTIFIED - NEC 408.4 4. PROVIDE A DISCONNECTING MEANS FOR WATER HEATER NEC 422.31 (B) 5. ALL OUTLETS IN BEDROOMS REQUIRE ARC FAULT PROTECTION INCLUDING LIGHTS, RECEPTACLES AND SMOKE DETECTORS - NEC 210.12 6. TIGHTEN ALL RECEPTACLES SO THEY ARE NOT LOOSE IN WALL -- NEC 406.4 7. COUNTER GFI BLOCKED BY REFER - NEC 210.52(C)(5) 8. MAKE SURE SMOKE DET. ARE MOUNTED PER THEIR INSTRUCTIONS -- NEC 110.3 |