Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
08/07/2006 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
02/16/2006 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
02/15/2006 ELECTRIC - PROGRESS Denied IVRS - Inspection :
The service is not per code.| 210*
1) FEEDER NEUTRALS NEED TO TERMINATE AT NEUTRAL LUGS AND FEEDER GROUNDS NEED TO TERMINATE ON GROUND LUGS-YOU HAVE THEM REVERSED-CORRECT THIS SAME PROBLEM ON OTHER BLDG SERVICE (#2)
01/24/2006 ELECTRIC - PROGRESS Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. STILL NEED PROTECTION THROUGH RATED WALLS AND FLOORS
01/20/2006 ELECTRIC - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NOT ALL CORRECTIONS COMPLETED ELECTRICIANS NOT ON SITE
2. IDENTIFY THREE WIRE NEUTRAL AS HOT WHERE USED
01/17/2006 ELECTRIC - PROGRESS Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*FIRE STOP ALL PENETRATIONS THROUGH RATED WALLS
GROUND ALL METAL BOXES
PROPERLY SECURE FEEDERS ( STRAP)
USE CONNECTORS WHERE FEEDER ENTERS PANELS
PLAN CALLS FOR ALL COPPER CONDUCTORS?
NEED SMOKE DETECTORS ON MAIN LEVEL
NEED TO DO A BETTER JOB OF STAPLING FOR ROMEX
OK TO COVER ELECTRICAL SECONDARY CONDUIT