Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2006 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
| 02/16/2006 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 02/15/2006 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The service is not per code.| 210* 1) FEEDER NEUTRALS NEED TO TERMINATE AT NEUTRAL LUGS AND FEEDER GROUNDS NEED TO TERMINATE ON GROUND LUGS-YOU HAVE THEM REVERSED-CORRECT THIS SAME PROBLEM ON OTHER BLDG SERVICE (#2) |
|
| 01/24/2006 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. STILL NEED PROTECTION THROUGH RATED WALLS AND FLOORS |
|
| 01/20/2006 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NOT ALL CORRECTIONS COMPLETED ELECTRICIANS NOT ON SITE 2. IDENTIFY THREE WIRE NEUTRAL AS HOT WHERE USED |
|
| 01/17/2006 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*FIRE STOP ALL PENETRATIONS THROUGH RATED WALLS GROUND ALL METAL BOXES PROPERLY SECURE FEEDERS ( STRAP) USE CONNECTORS WHERE FEEDER ENTERS PANELS PLAN CALLS FOR ALL COPPER CONDUCTORS? NEED SMOKE DETECTORS ON MAIN LEVEL NEED TO DO A BETTER JOB OF STAPLING FOR ROMEX OK TO COVER ELECTRICAL SECONDARY CONDUIT |