Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2005 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 03/30/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TO POUR SIDEWALK. OK 2 GROUND RODS & 3/0 COPPER | |
| 03/29/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :*OK 4 POLE BASES. 1) CONNECTIONS TO GROUND RODS TO BE LISTED FOR 3/0 | |
| 03/25/2005 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) 20' COIL TO BE AT BOTTOM OF HOLE-CONDUCTOR TO BE STRAIGHT AS POSSIBLE DOWN TO BOTTOM 2) CONDUIT TO HAVE 18" OF COVER 300.5 3) GROUND CONDUCTOR TO BE #2 AS PER PLANS 4) PLANS DO NOT CALL FOR CONNECTION TO ?. PLEASE DISCONNECT CLAMP FROM ? |
|
| 03/04/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK FEEDER CODUITS BUILDING TO SERVICE OK PHONE CONDUITS BUILDING TO D MARK | |
| 02/23/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK PARKING LOT FEEDERS- LEAVE BOXES OPEN. 2) OK 1-4" PVC FOR SERVICE FROM BLDG TO WITH IN 20' OF ?. 3) OK 3-1/2" PANEL FEEDERS FROM SERVICE TO EAST SIDE OFF BLD LEAVE ENDS OPEN. 4) OK 3-2" PHONE LINES SAME AS ABOVE-LEAVE ENDS OPEN. | |
| 10/19/2004 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* |