Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04CM04027

Parcel: 121090090


Addresses:

5357 E PIMA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/01/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/29/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE IN NON COMBUSTIBLE NEED AN APPROVED EXTENDER RING 370.20/314.20. 2) PROVIDE MANUFACTURER'S INSTRUCTION FOR BATH LIGHT. MISSING BACK PLATE. 3) LABEL DISCONNECTS AND PANELS AND BREAKERS. 4) ONLY ONE CONDUCTOR PER TERMINAL LOG. 5) BOND DISCONNECT ENCLOUSER. 6) FILL UNUSED OPENINGS. 7) IDENTIFY GROUNDING CONDUCTOR. 9) NEED GROUND BAR AT PANEL. 10) RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGED IN TO 406.8. 11) CHASE NIPPLE NOT APPROVED FOR FITTING TO BOX ROOF. 12) TIGHTEN LOOSE FITTINGS. 13) DISCONNECT NOT TO BE MOUNTED TO ACCESSABLE PANELS 440.14