Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/01/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 03/29/2005 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE IN NON COMBUSTIBLE NEED AN APPROVED EXTENDER RING 370.20/314.20. 2) PROVIDE MANUFACTURER'S INSTRUCTION FOR BATH LIGHT. MISSING BACK PLATE. 3) LABEL DISCONNECTS AND PANELS AND BREAKERS. 4) ONLY ONE CONDUCTOR PER TERMINAL LOG. 5) BOND DISCONNECT ENCLOUSER. 6) FILL UNUSED OPENINGS. 7) IDENTIFY GROUNDING CONDUCTOR. 9) NEED GROUND BAR AT PANEL. 10) RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGED IN TO 406.8. 11) CHASE NIPPLE NOT APPROVED FOR FITTING TO BOX ROOF. 12) TIGHTEN LOOSE FITTINGS. 13) DISCONNECT NOT TO BE MOUNTED TO ACCESSABLE PANELS 440.14 |