Permit: T04CM04026

Parcel: 10511061R

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04CM04026

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/09/2004 PLUMBING - FINAL Approved
12/08/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/1)REQUIRE BACKFLOW CERTIFICATION ON DEVICES. 2)TRAPS FOR INDIRECT WSTE PIPING TO BE SET TRUE, PLUMB, AND WITH 1/4" PITCH PER FOOT-CHANGES OF DIRECTION REQUIRE CLEAN-OUTS
12/07/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/1)REQUIRE BACKFLOW PROTECTION FOR SUBMERGED INLET ON WOKS 2)1/2" SUPPLY REQUIRED FOR WOKS-ALL INTEGRAL PIPING AND CONNECTIONS ON WOK ARE 1/2" 3)PVC TRAP AT FRONT COUNTER IS SKEWED-CAUSING LOSS OF TRAP SEAL. ALL DRAINAGE PIPING TO BE INSTALLED AT 2% 4)REQUIRE MINIMUM 1" AIR GAP AT ALL INDINET DRAINS CERTIFICATION REQ'D FOR BACKFLOW DEVICES 5)UNABLE TO LOCATE APPROVED REVISED PLAN
12/03/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*