Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T04CM04026
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2004 | PLUMBING - FINAL | Approved | ||
12/08/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/1)REQUIRE BACKFLOW CERTIFICATION ON DEVICES. 2)TRAPS FOR INDIRECT WSTE PIPING TO BE SET TRUE, PLUMB, AND WITH 1/4" PITCH PER FOOT-CHANGES OF DIRECTION REQUIRE CLEAN-OUTS | |
12/07/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/1)REQUIRE BACKFLOW PROTECTION FOR SUBMERGED INLET ON WOKS 2)1/2" SUPPLY REQUIRED FOR WOKS-ALL INTEGRAL PIPING AND CONNECTIONS ON WOK ARE 1/2" 3)PVC TRAP AT FRONT COUNTER IS SKEWED-CAUSING LOSS OF TRAP SEAL. ALL DRAINAGE PIPING TO BE INSTALLED AT 2% 4)REQUIRE MINIMUM 1" AIR GAP AT ALL INDINET DRAINS CERTIFICATION REQ'D FOR BACKFLOW DEVICES 5)UNABLE TO LOCATE APPROVED REVISED PLAN | |
12/03/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |