Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL RECEIVED LETTER FOR AREA USAGE. | |
| 05/31/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) A LETTER FOR USAGE OF AREA TO STATE. NON ??NG VEHICLES USE FROM OWNER CAN BE SUBMITTED FOR # 1 OF PREVIOUS INSPECTIONS PER RAY MAJUTA | |
| 05/26/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) APPROVED EXTENDER RINGS ARE NEEDED WHERE BOXES NOT FLUSH IN COMBUSTIBLE SURFACES 314.20 (METAL NOT APPROVED) 2) PLEASE PROVIDE METER AND DISCONNECT LABELING AND ADDRESSING-PANEL COVERS 3) WE HAVE MULTIPLE TERMINATION ? MAIN DISCONNECT GROUND BAR 4) PLEASE COMPLETE #1 OF INSPECTION DATED 4/20/05 5) LB COVER TO BE ACESSIBLE 6) AREA OCCUPIED WITHOUT FINAL INSPECTIONS |