Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM04009
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/18/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO CLEAR 7950 E STELLA BLDG K UNITS 15 & 16 | |
04/01/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSTALL N.M. CONNECTOR WHERE 10/2 WIRE ENTERS INTO A.C UNIT |
|
03/29/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL APPLIANCES ( HOOD, D.W, RANGE) 2) INSTALL N.M CONNECTOR AT HALL A.C UNIT. 3) OPEN LAMP FIXTURES ARE NOT ACCEPTABLE IN CLOSET. 4) PLEASE INSTALL SMOKE DETECTORS IN BEDROOMS ( BATTERY WILL BE O.K.) |
|
12/20/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |