Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM04008
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/03/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/28/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) MAINTAIN WIRE BONDING RADIUS 2) NEED REJECTION PINS AT SERVICE 3) LABEL DISCONNECT. POWER IS ENERGIZED BY CONTRACTOR 4) FINISH ITEMS # 1 AND 3 OF PREVIOUS INSPECTION 5) OK TO TILE EXCEPT AS NOTED AND DISCUSSED | |
10/25/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) FIXTURE WHIPS WHERE SUPPORTED, M/C CABLES, CONDUITS AND BOXES TO BE SUPPORTED BOTH ENDS 300.11 2) EXHAUST FANS TO BE ATTACHED TO GRID AND TIGHTEN LOOSE FITTINGS 3) PROPERLY SUPPORT VDV CABLES (THERMOSTAT) AS PER CODE 725.6 4) ? IS NOT AN PAROOVED SUPPORT METHOD 5) WHAT CONDUITS ARE EXISTING, WHAT ARE NEW |