Permit: T04CM03938

Parcel: 125041070


Addresses:

2034 E 1ST ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/02/2005 FRAMING Approved IVRS - Inspection :*
01/21/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) FLEX GAS CONNECTOR CANNOT PENETRATE MECHANICAL FIRE PLACE CABINET
2) FIRE BLOCK MISSING KITCHEN BY GAS LINE
3) NO DWV WATER TEST ON PLUMBING
4) ALL WIRES MUST TERMINATE IN APPROVED ELECTRIC BOXES KITCHEN
5) NAIL PROTECT PLUMBING AND ELECTRIC WITHIN 1 1/4" OF STUD WALL SURFACE
6) PEX PLUMBING NOT ALLOWED WITHIN 12" OF RECESSED LIGHTS MASTER BATH AND THROUGHOUT
7) SANITARY "T" FITTING CANNOT BE USED AS DRAIN FITTINGS IN MASTER BATH
8) MAKE UP ALL GROUND WIRES IN BOXES AND CONNECT WITH MECHANICAL FASTENERS
9) PROVIDE WATER HEATER VENT AND COMBUSTION AIR AND T & P FOR GARAGE WATER HEATER
10) PROVIDE SOFFIT FOR PLUMBING AND ELECTRIC OUT OF WALL
11) STAIRS HAVE OPENINGS LARGER THAN 4"
12) INSULATE DUCT WYES
13) GROUND ALL METAL ELECTRIC BOXES
14) W/H T & P LINE MUST EXHAUST OUTSIDE
15) DRAFT STOP MECHANICAL PLATFORM
16) BOND GAS LINE
01/10/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
1) COMPLETE STUCCO MESH BEFORE INTERMEDIATE INSPECTIONS
12/06/2004 FRAMING Not ready for Inspection IVRS - Inspection :*