Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/23/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* I TESTED SOME OF YOUR RECEPTS NOT ALL EAST WALL IN CORRECT WIRING STARTING AT GFCI, EFFECTS EVERYTHING DOWN STREAM NORTH WALL NOT ALL RECEPTS ARE GFCI PROTECTED NEED G.E 100 AMP IN SERVICE |
|
| 03/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SOME RECEPTS GFCI PROTECTED WON'T TRIP WHERE TESTED 2) SUB-PANEL SCHEDULE ON PLAN SHOWS 4 CIRCUITS-YOU HAVE ELEVEN 20 AMP 2-2 POLE 30 AMP 3) GROUND BUSS NEED TO BE BONDED TO PANEL CABINET 4) YOU HAVE AN ? PANEL WITH DIFFERENT BREAKERS NOT APPROVED FOR THAT PANEL 5) NEED BUBBLE COVERS ON EXTERIOR RECEPTS 6) THERE IS A LIGHTING CODE, FOR SHIELDED AND UNSHIELDED EXT. LIGHT FIXTURES, I COULDN'T FIND YOUR CALC ON ELECTRIC PLAN ? 7) VERIFY 100 AMP BREAKER IN EXISTING HOUSE PANEL 8) CANNOT SPLICE #4 CU WITH A WIRE NUT, REQUIRES A DIFFERENT CLAMP CONNECTION |