Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04CM03921

Parcel: 135080170

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/29/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/23/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
I TESTED SOME OF YOUR RECEPTS NOT ALL EAST WALL IN CORRECT WIRING STARTING AT GFCI, EFFECTS EVERYTHING DOWN STREAM
NORTH WALL NOT ALL RECEPTS ARE GFCI PROTECTED

NEED G.E 100 AMP IN SERVICE
03/10/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SOME RECEPTS GFCI PROTECTED WON'T TRIP WHERE TESTED
2) SUB-PANEL SCHEDULE ON PLAN SHOWS 4 CIRCUITS-YOU HAVE ELEVEN 20 AMP 2-2 POLE 30 AMP
3) GROUND BUSS NEED TO BE BONDED TO PANEL CABINET
4) YOU HAVE AN ? PANEL WITH DIFFERENT BREAKERS NOT APPROVED FOR THAT PANEL
5) NEED BUBBLE COVERS ON EXTERIOR RECEPTS
6) THERE IS A LIGHTING CODE, FOR SHIELDED AND UNSHIELDED EXT. LIGHT FIXTURES, I COULDN'T FIND YOUR CALC ON ELECTRIC PLAN ?
7) VERIFY 100 AMP BREAKER IN EXISTING HOUSE PANEL
8) CANNOT SPLICE #4 CU WITH A WIRE NUT, REQUIRES A DIFFERENT CLAMP CONNECTION