Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/06/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) FRAMING WILL BE APPROVED WHEN ALL TRADES ARE COMPLETE 2) MOVE 10-3 WIRE AWAY FROM GUSSET AND 8-3 WIRE 3) ROMEX RUNNING OVER EXHAUST FAN IN LAUNDRY, CUT 4) SEAL LATH PENETRATION AT MASTER CLOSET, CONDENSOR LINES MOVED. SEAL AT WATER LINE (MAIN) 5) MOVE WATER LINE AWAY FROM GUSSET 6) ELECTRICAL WIRE HANGING BELOW CEILING LINE IN LIVING ROOM |
|
| 01/05/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRIC BOX HANGING UNDER EAVE 2) GAS PRESSURE TEST AT 0 PSI 3) SECURE ROMEX WITHIN 8" FROM WALLS 4) MOVE DRYWALL AWAY FROM EXTERIOR WALLS TO INSPECT |
|