Permit: T04CM03913

Parcel: 124170540

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/30/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
03/21/2007 PLUMBING - FINAL Not ready for Inspection CONDENSATE TO LAV HAS BEEN CAPPED OFF TO CORRECT PLUMBING PROBLEM AT P-TRAP
PIPE CONDENSATE TO APPROVED LOCATION

218-07
03/20/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
REMOVE ROCKS FROM TOP OF PIPING
USE CLEAN BACKFILL
CORRECT 6" DEEP UNAPPROVED P-TRAP
03/14/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
10' OF EXPOSED YARD WATER
1. EXPOSE ALL YARD WATER PIPING AND CALL FOR 03040 INSPECTION
2. SUPPORT BELOW GRADE PIPING W/CLEAN FILL DIRT
3. INSTALL TRACER WIRE PER STATE STATUTE
02/09/2007 PLUMBING - FINAL Cancelled CANCELLED PER JUAN
02/06/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/16/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
LOCKED
SEE NOTES FROM PREVIOUS INSP.
HAVE UNAPPROVED INSP APPROVED
CORRECT T&P
08/09/2006 PLUMBING - FINAL Cancelled CANCELLED BY PHONE CALL
08/09/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- YOU HAVE NOT COMPLETED ANY OF THE NECESSARY CORRECTIONS FROM THE INSPECTION ON 8/7/06
- FOR THAT REASON A REINSPECTION FEE HAS BEEN ASSESSED.
- THE FEE MUST BE PAID WITHIN 5 DAYS.
- AFTER 5 DAYS A HOLD WILL BE PLACED ON ANY FURTHER INSPECTIONS.
- NO FINAL INSPECTIONS CAN BE SCHEDULED OR PERFORMED IF THERE ARE ANY UNPAID REINSPECTION FEES.

ALSO, PLANS ON SITE DO NOT REFLECT WORK
HAVE APPROVED PLANS FOR THIS JOB ONSITE AT ALL TIMES.
08/07/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXPOSE YARD WATER LINE AND CALL FOR INSPECTION.
2. WATER SHALL BE ON FOR INSPECTIONS
3. LOCATE AND EXPOSE EXTERIOR SEWER CLEAN OUTS SHALL BE TO GRADE.
4. LAV P-TRAP NOT PROPERLY INSTALLED
5. T&P RELIEF FROM WH SHALL TERMINATE OUTSIDE, GRAVITY DRAIN.
6. DW & HOSE NOT PROPERLY INSTALLED
7. PROVIDE CLEANOUT PLUGS LISTED TO RECEIVE SCREW FROM COVER.
06/28/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*1) DWV WATER TEST IS OK. 2) OVERHEAD WATER DISTRIBUTION IS OK. 3) OK TO DRY WALL.
06/09/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
04/22/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* 1) ABS SEWER FROM CONNECTION AT MAIN( CUT IN FITTING, NO SADDLE TAP) TO BLDG OK. WATER TEST OK OK TO COVER CONTRACTOR TO SHADE PIPE WITH 6" OF CLEAN FILL.