Permit: T04CM03891

Parcel: 11005014C


Addresses:

2900 N SWAN RD #100


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T04CM03891

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/29/2005 MECHANICAL - FINAL Approved IVRS - Inspection :* OK FOR FINAL C OF O
03/14/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :* PROVIDE GREASE CUPS ON EXHAUST FANS. DRAIN ON EVAP COOLER RUNS UPHILL. EXTEND WATER HEATER VENT TO 3' ABOVE EVAP COOLER. SECURE VENT PIPE.
02/15/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :* PROVIDE MIN. 1" CLEARANCE AT WATER HEATER VENT THRU ROOF. RELOCATE ELEC CABLE. CLEANOUT ACCESS DOORS NOT LARGE ENOUGH ON GREASE DUCTS. EXTEND FIRE WRAP ALL THE WAY TO TOP OF GREASE DUCT. PROVIDE A DRAIN ON MAKE UP AIR UNIT. PROVIDE GREASE CUPS ON EXHAUST FANS.
02/10/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :* CLEANOUT OPENINGSMUST BE MIN 12" ON EACH SIDE. SEE SECTION 506.6 IMC. OK FOR CEILING TILES. LEAVE OUT UNDER GREASE DUCT ACCESS DOORS. FINISH WATER HEATER VENTING. OK FOR TEMP C OF O.