Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM03891
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/18/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
02/09/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PARTIAL OK KITCHEN LIGHTS 1) FINISH CABLEING AS DISCUSSED | |
02/01/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PARTIAL WALL BEHIND BAR-OK NORTH WALL OK | |
01/07/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* O.K. BATHHROOM WALLS | |
12/21/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*PARTIAL APPROVAL-1) JUNCTION BOXES WILL NEED ACCESS. 2) SUPPORT VDV CABELING PER 725.6 AND 800.6 OR AS PER 725.2 AND D800.2. OK DINING AREA 101 SUBJECT TO REVISED PLANS. | |
12/13/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :FILL UNUSED OPENINGS IN BOXES PROTECT M/C CABLE IN CHANGE STUDS DO NOT BUNDLE M/C CABLE AS PER CODE FINISH SUPPORTING M/C CABLE |