Permit: T04CM03891

Parcel: 11005014C


Addresses:

2900 N SWAN RD #100


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T04CM03891

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/18/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/09/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* PARTIAL OK KITCHEN LIGHTS 1) FINISH CABLEING AS DISCUSSED
02/01/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* PARTIAL WALL BEHIND BAR-OK NORTH WALL OK
01/07/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* O.K. BATHHROOM WALLS
12/21/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*PARTIAL APPROVAL-1) JUNCTION BOXES WILL NEED ACCESS. 2) SUPPORT VDV CABELING PER 725.6 AND 800.6 OR AS PER 725.2 AND D800.2. OK DINING AREA 101 SUBJECT TO REVISED PLANS.
12/13/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :FILL UNUSED OPENINGS IN BOXES
PROTECT M/C CABLE IN CHANGE STUDS
DO NOT BUNDLE M/C CABLE AS PER CODE
FINISH SUPPORTING M/C CABLE