Permit: T04CM03884

Parcel: 140292450


Addresses:

6292 S EARP WASH LN


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM03884

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
12/28/2004 FRAMING Approved IVRS - Inspection :*
12/20/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COVERED WITH INSULATION UNABLE TO INSPECT
12/13/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STUCCO LATH REQUIRES REINFORCEMENT ON CORNERS
2) STUCCO NOT NAILED ON ? OF HOUSE
3) OVER BORED DOUBLE TOP PLATES REQUIRE FASTENERS NAILED WITH 12-16D NAILS
4) FIRE BLOCK DROP CEILINGS/SOFFITS
5) GARAGE DBL G1 SHEAR REQUIRES SHEAR BEHIND SOFFIT
6) GARAGE SHEAR WALL REQUIRED TO BE 13'-6" ONLY 13'-0"
7) NO GAS BOND
8) FURNACE ? HORIZONTAL RUN CANNOT EXCEED 3/4" OF RISE
9) MASTER BATH EXCEED 1 1/2" DIAMETER OR 42" IN LENGTH
10) SECURE ELECTRIC WIRES WITHIN 8" OF BOXES