Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM03884
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/28/2004 | FRAMING | Approved | IVRS - Inspection :* | |
12/20/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COVERED WITH INSULATION UNABLE TO INSPECT |
|
12/13/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STUCCO LATH REQUIRES REINFORCEMENT ON CORNERS 2) STUCCO NOT NAILED ON ? OF HOUSE 3) OVER BORED DOUBLE TOP PLATES REQUIRE FASTENERS NAILED WITH 12-16D NAILS 4) FIRE BLOCK DROP CEILINGS/SOFFITS 5) GARAGE DBL G1 SHEAR REQUIRES SHEAR BEHIND SOFFIT 6) GARAGE SHEAR WALL REQUIRED TO BE 13'-6" ONLY 13'-0" 7) NO GAS BOND 8) FURNACE ? HORIZONTAL RUN CANNOT EXCEED 3/4" OF RISE 9) MASTER BATH EXCEED 1 1/2" DIAMETER OR 42" IN LENGTH 10) SECURE ELECTRIC WIRES WITHIN 8" OF BOXES |