Inspection History Details
Inspection Status: Approved
Inspection History: ROOF NAILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2005 | ROOF NAILING | Approved | IVRS - Inspection :* | |
| 03/04/2005 | ROOF NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO CHANGE FROM 3/3/05 INSPECTION 2) IF YOU HAVE QUESTIONS (SPANISH) PLEASE CALL HENTRY DURAZO 954-0152 |
|
| 03/03/2005 | ROOF NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE TRUSS LAYOUT PLAN 2) PROVIDE T3G TRUSS DRAWING 3) T3 TRUSSES ARE NOT PER DRAWINGS, ALL HAVE DEAD WOOD/DROP CEILINGS WITH NO PROVISION FOR BRACING BOTTOM CHORDS. PROVIDE EXACT DRAWINGS FOR TRUSSES 4) X BRACE EAST GABLE END 5) X BRACE MIDDLE-UFER 25 FEET BETWEEN BRACES 6) ROOF SHEATHING NAILING OK |
|
| 03/01/2005 | ROOF NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PERMIT CARD 2) NO APPROVED TRUSS DRAWINGS 3) STOPPED INSPECTION |