Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2004 | FRAMING | Approved | IVRS - Inspection :* | |
| 12/08/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL BLOCK BETWEEN HI-LOW COMBUSTION OPENINGS IN GARAGE 2) TIGHTEN ANCHOR BOLTS ? WALLS 3) REPAIR TOP PLATE AT DRYER VENT 4) WIRE MUST BE INSULATED TO INTERIOR OF BOX IN HALLWAY BY GARAGE 5) GROUND EXTERIOR METAL BOXES 6) NAIL PROTECT VENT STACK MASTER BEDROOM WATER CLOSET 7) NAIL PROTECT TUB VENTING SECOND TUB 8) FIRE BLOCK KITCHEN EXHAUST 9) COMPLETE ARCH WAYS TO KITCHEN AND HALL WAY 10) SHIM ALL BEARING HEADERS 11) WATER TESTS OK |
|
| 12/06/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |