Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04CM03838

Parcel: 137340030


Addresses:

1640 W VALENCIA RD


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T04CM03838

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/10/2005 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
10/18/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*EXHAUST HOOD DUCTS-CLEAN UP DUCTS CONNECTION AT POINT OF ATTACHMENT TO HOODS. SHOULD BE CLEAN SMOOTH EDGE.
WANT TO SEE 1ST WRAP OF FIREWRAP PRIOR TO 2ND.
FIREWRAP CONTINUES UP INTO TOP OF CURL OR 18" PAST COMBUSTIBLES
SUPPLY DUCTS IN SOFFITS, OK, SEALED. OK TO START WRAP.