Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2005 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/18/2005 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*EXHAUST HOOD DUCTS-CLEAN UP DUCTS CONNECTION AT POINT OF ATTACHMENT TO HOODS. SHOULD BE CLEAN SMOOTH EDGE. WANT TO SEE 1ST WRAP OF FIREWRAP PRIOR TO 2ND. FIREWRAP CONTINUES UP INTO TOP OF CURL OR 18" PAST COMBUSTIBLES SUPPLY DUCTS IN SOFFITS, OK, SEALED. OK TO START WRAP. |