Permit: T04CM03838

Parcel: 137340030


Addresses:

1640 W VALENCIA RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04CM03838

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/08/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
RECEIVED ALL BACKFLOW CERTS - ALL CORRECTIONS HAVE BEEN MADE
12/01/2005 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) OK FOR TEMP C OF O PER STEVE LONG'S APPROVAL
2) 1 ADDITIONAL DBL CHECK ASSEMBLY TO BE INSTALLED AT POTABLE WATER DISTRIBUTION AREA TO SEPERATE BAR GUNS (2) FROM SODA FOUNTAINS (2)
3) PROVIDE CERTIFICATION PAPERWORK FOR ALL BACKFLOW ASSEMBLERS
4) SUPPORT HOT AND COLD PIPING AT WATER HEATER CONNECTIONS
5) CORRECT SOLDIER LEAK AT SOFTNER
6) SEPERATE RINSE AND WASH COMPARTMENTS ON 3 COMP SINK FROM SANITIZE COMPARTMENT
7) SEPERATE DISH WASHER, FROM HAND DRAIN
8) PROVIDE CLEANOUTS AND WYE BRANCH (LONG-RADIUS) FITTINGS ON INDIRECT DRAIN PIPING A SAN T ON IT'S BACK IS NOT AN EXCEPTABLE INSTALLATION
9) DRAINAGE PIPING MUST BE THE SAME SIZE AS THE OUTLET
10) UV PROTECTION REQUIRED FOR EXPOSED PLASTIC PIPING
11) REMOVE TEMP CLEANOUT PLUGS AND INSTALL TAPPED CLEANOUT PLUGS WITH MACHINE SCREW
7)
11/28/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*BACKFLOW PROTECTION REQUIRED FOR CARBONATORS, COFFE & TEA BREWING EQUIPTMENT, AND ICE MAKER.
11/23/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* TEST AND PIPING TO NEW HAND SINK ?? DISHWASHING AREA OK TO COVER
WILL NEED APPROVED PLAN FOR CHANGE.