Permit: T04CM03838

Parcel: 137340030


Addresses:

1640 W VALENCIA RD

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
11/21/2005 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection :*PARTIAL APPROVAL 10 PSI AIR TEST ALL PIPING OK
MAKE CORRECTIONS PER 11/16/05 INSPECTION AND SUPPORT ALL PIPING CORRECTLY
11/21/2005 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection :*
11/18/2005 PLUMBING - GAS PRESS TEST FNL Partial Approval IVRS - Inspection :*
11/16/2005 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE UNIONS AT ? VALVES LOCATED ABOVE GRID CEILING
2) INSTALL T & P ? VALVES ON W H
3) SECURE PIPING DROPS ON GAS SUPPLY TO W H
4) REMOVE VALVES BETWEEN WHS AND EXPANSION TANK