Permit: T04CM03838

Parcel: 137340030


Addresses:

1640 W VALENCIA RD

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
11/16/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*10 PSI PRESSURE TEST ON INTERIOR GAS PIPING OK
CALL FOR GAS FINAL TO GET APPROVAL FOR METER CONNECTION. ABOVE CEILING OK TO COVER
11/07/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) 70 PSI TEST FROM METER TO 1 1/2 STUBBED INTO WATER HEATER ROOM OVERHEAD, UP TO ROOF TO (3) AHU'S WITH (1) 2" DROP DOWN INTO KITCHEN CAPPED AT WALL AND (1) 1 1/4" DROP DOWN INTO KITCHEN CAPPED AT WALL. 1 1/4 KITCHEN PIPE TO BE SECURED. 1 1/4" PIPING TO AHU #3 TO HAVE SHUT OFF VALVE WITHIN 3' OF APPLIANCE AND CAP ON DRIP LEG SHALL NOT CONTACT ROOF
11/03/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/26/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*3" MAIN GAS FROM METER TO STUB UP AT ROOF INCLUDING 1 1/2 T-O-L FRO WATER HEATERS OK
10/24/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*