Permit: T04CM03838

Parcel: 137340030


Addresses:

1640 W VALENCIA RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T04CM03838

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
07/11/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
1) DWV WATER TEST IS OK
2) BLDG DRAINS HAVE BEEN STUBBED AT TWO WAY CLEANOUT
3) ALL CORRECTIONS HAVE BEEN MADE
4) OK TO BACKFILL TRENCH
07/08/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :* 1) HAD MEETING WITH PLBG CONTRACTOR ON THE COMBINATION WASTE & VENT SYSTEM
07/07/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) SHALL PROVIDE A DIRECTIONAL FITTING FOR FLAT VENT @ COMBINATION WASTER & VENT SYSTEM. 2) SHALL REDUCE TAIL PC @ TOP OF WIER OF TRAPS BY TWO PIPE SIZES FOR C.W.V SYSTEM. 3) SHALL LOCATE VENT IN VERTICAL POSITION FOR FLOOR SINK @ NORTH WEST CORNER OF BLDG. 4) 2" HORIZONTAL WASTE LINE FOR LAVATORY IN MEN RESTROOM EXCEEDS 135 DEGREE CHANGE OF DIRECTION. C.O. REQUIRED WHERE IT EXCEEDS. 5) SHALL PROVIDE A FULL SIZE VENT FOR C.W.V SYSTEM @ SOUTH EAST CORNER OF BLDG 6) SHALL STAKE ALL DRAINS & VENTS WITH NO SHADE.
03/28/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :* FROM DISCHARGE SIDE OF 2" ? RISER AT BACKFLOW LOCATION TO 5' FRO BLD SERVICE 60 PSI AIR TEST OK. 1) WILL NEED TO SEE CONNECTION TO BUILDING. 2) CONNECTION OF BACKFLOW DEVICE. 3) TEST ON PIPING FROM METER LOCATION TO AND THRU BACKFLOW DEVICE.
03/21/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :* 1) 2" C.W. SUPPLY FROM METER LOCATION TO 5' OF BLDG SERVICE IS OK TO BACKFILL TRENCH. 2) SHALL PROVIDE A AIR PRESSURE TEST ON ENTRIE 2" WATER SERVICE.