Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO CLEAR UPGRADE INTERIOR REMODEL NO BOND REQD APPROVED | |
| 12/30/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BATH LIGHT TO BE MADE UP IN BOX & BOX TO BROUGHT TO SURFACE NOT COVERED WITH DRY WALL. 2) PLANS CALL FOR MAIN CIRCUIT BREAKER AT PANEL " B". 3) BONDING JUMPER TO BE SIZED PER 250. 102 & 250.66 4) NEED REJECTION PINS AND FUSES. 5) WHEATHER PROOF COVERS TO BE WEATHER OR NOT PLUGED IN 406.8 6) TIGHTEN LOOSE LIQUID TITE FITTINGS 7) LABEL DISCONNECTS 8) SERVICE CONDUCTOR TO BE LISTED SUNLIGHT RESISTANT 310.2 | |
| 12/29/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) NEED EXTERIOR LIGHT FIXTURE AND CIRCUIT DIRECTORY IN PANEL-"B" 2) RENUMBER PANEL "B" TO MATCH THE PLAN PANEL SCHEDULE OR REVISE PLAN |