Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* APPROVED | |
| 08/20/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :the electrical service equipment and sub-panel are not of the type NOTEDON THE PLAN THE USE OF MC CABLE IS NOT APPROVED PER PLAN SPEC'S/ SPEC'S REQUIRE EMT WHERE WILL WATER HEATER BE LOCATED? GOUND BONDING IS INCOMPLETE TO KEEP THE INSTALLATION OF THE SERVICE EQUIP LOAD CENTER PANEL AND MC CABLE YOU MUST PROVIDE A REVISED PLAN STAMPED/ SEALED BY THE ENGINEER OF RECORD AND HIS LETTER APPROVING THE USE OF MC CABLE IN LEIU OF THE SPEC'D EMT |