Permit: T04CM03823

Parcel: 11515284A


Addresses:

2209 N 15TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/31/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/29/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL ALL FACTORY SCREWS IN PANEL COVER & INSTALL K.O BLANK.
2. IDENTIFY ROOFTOP UNITS AND THEIR DISCONNECTS & INSTALL K.O BLANK
3. ROOF EXH. FAN DISCONNECT SWITCH IS STUCK IN ON POSITION.
4. TIGHTEN ALL LOOSE RECEPTACLES
5. USE EQUIPMENT GROUND TO GROUND ALL METAL ENCLOSURES NEXT TO PANEL.
6. FINISH ALL WIRING INCLUDING LOW VOLTAGE & INSTALL COVERS.
PARTIAL INSPECTION ONLY.