Permit: T04CM03823

Parcel: 11515284A


Addresses:

2209 N 15TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
07/26/2005 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
07/21/2005 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEC-300 MINIMUM BURIAL DEPTH
2) 18" TO TOP OF PIPE
3) RUN BETWEEN NEW BLDG AND SCHOOL ONLY 16" IN SOME PLACES
4) 2 1/2" PVC FEEDER 10' FROM SERVICE TO NORTH SIDE OF BLDG SERVICE-OK
5) 5-2" PVC'S NEW BLDG TO SERVICE TO EXISTING SCHOOL OK
03/25/2005 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) ALL UNDERGROUND WITHIN BLDG