Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 12/15/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CHASE NIPPLE NOT APPROVED WITH LB. ALSO NEED BOND BUSHING AT SERVICE 2) BONDING JUMPERS TO BE SIZED PER 250.102 AND 250.66, 110.3 AND 250.92 |
|
| 12/13/2004 | ELECTRIC - FINAL | Cancelled | ||
| 12/13/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/10/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FILL UNUSED OPENING IN BOXES 2) LIGHTING NOT AS PER PLAN 3) TELE BOARD, RECEPTACLE AND CONDUITS NOT RUN 4) SUPPORT CONDUITS AS PER CODE ABOVE PANEL 5) FINISH SERVICE-NOT AS PER CODES |