Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 02/11/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE INSPECTION DATED 2/10/05 |
|
| 02/10/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXHAUST FAN IN HALL BATH MISSING FLAPPER AND SCREEN AT T-TOP 2) TRIPPLE GIRDER DRILLED AND NOTCHED IN FIVE AREAS AT BOTTOM CHORD 3) ELECTRIC WIRE CUT AT SHEAR PANEL AREA 4) FRAMING WILL BE APPROVED WHEN ALL TRADES ARE COMPLETE 5) ELECTRIC BOX (JUNCTION) MUST BE ACCESSIBLE AT FIREPLACE |
|
| 01/28/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1 PROVIDE 1" CLEARANCE AT FURNACE AT B-VENT 2 EXHAUST FAN IN HALL BATH IS MISSING AND SCREEN AT T-TOP 3 ELEC WIRE CUT? AT SHEER PANEL AREA 4 PROVIDE CLARIFICATION FOR DETAIL 2SD2 |
|
| 01/25/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INTERIOR SHEAR NOT NAILED TO DBL TOP PLATE 2) SECURE WATER LINES AT MASTER BATH 3) FITTING FOR VTR AT HALL BATH LEAKING AND SUPPORT VTR'S IN ATTIC SPACE 4) PROVIDE SMOKE DETECTOR OUTSIDE BEDROOMS 5) NAIL PROTECT ELECTRIC AT TRIPPLE GIRDER AREA 6) PROVIDE REPAIR FOR TRIPPLE GIRDER 7) A10A TRUSS BONDED 8) LEAK AT LAUNDRY ROOM, POWDER ROOM AND ABOVE DINING ROOM 9) MISSING 2-2 X 6 AT GLB KITCHEN 10) NAIL PROTECT PLUMBING AT GARAGE 11) COMPLY WITH DETAIL 1ASD2 12) COMPLY WITH LTR DATED 1/11/05 FOR REPAIR OF INTERRUPTED TOP PLATES |