Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/02/2005 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* | |
| 08/08/2005 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT HAVE SCHEDULE 80 NIPPLE SCREW INTO A PLASTIC FEMALE APPT. |
|
| 08/05/2005 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SHALL REMOVE BLK NIPPLE AND PROVIDE GALV. NIPPLE @ METER CONNECTION |
|
| 08/02/2005 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* 1) SHALL EXPOSE 2" WATER SERVICE AT BACKFLOW PREVENTOR |
|
| 07/20/2005 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) METER IS NOT CONNECTED, NO ONE ON SITE |
|
| 02/25/2005 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 2 1/2" T/K SILVER SOLDERED UNDER SCHB 60 + PSI AIR TEST STUBBED OUT OF BUILDING 5' OK. PIPE WRAPS & PRIMERS & SLEEVES OK FOR POUR 1) TESTING OF WASTE & VENT BELOW SLAB WILL BE NECESSARY BECAUSE ALL PIPE PENETRATIONS ARE CUT DOWN BELOW SLAB |