Permit: T04CM03815

Parcel: 11449030A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/21/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/17/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*PLEASE CHANGE OUT CUTLER HAMMER BREAKER IN SIEMENS PANEL
CHECK DISCONNECT HANDLE OPERATION-NOT SAFETY RELEASE
11/14/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) IDENTIFY GROUNDING CONDUCTORS 250.119
2) IDENTIFY UNGROUNDED CONTRACTORS PER CITY AMENDMENT BROWN, ORANGE AND YELLOW
3) PLEASE CHECK OPERATION OF DISCONNECT-HARD TO OPEN
4) SECURE TRANSFORMER TO PAD
5) INSTALL MAIN BONDING JUMPER AT TRANSFORMER
6) CLEAN SURFACES UNDER LUGS
7) FILL EXCESS OPENING WHERE CONDUITS ENTER TRANSFORMER
8) LABELING TO MATCH PLANS
9) USE PROPER HARDWARE/CLOSURERS FOR PANEL COVERS
10) USE BREAKERS LISTED FOR USE BY MANUFACTURER
09/09/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK FOR TEMP C OF O SUBJECT TO OTHER INSPECTIONS
2) WAITING ON MODULAR BLDGS
09/09/2005 ELECTRIC - FINAL Partial Approval OK FOR TEMP C OF O
09/08/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH PREVIOUS ITEMS 2, 9, 6 AND 10
09/07/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING TIME CLOCK
2) SUPPORT M/C AS PER CODE
3) SUPPORT UDV CABELING AS PER CODES
4) LABEL WATER HEATER DISCONNECT
5) MAINTAIN WORK CLEARANCES IN FRONT OF A/C DISCONNECTING MEANS
6) MAKE UP EXHAUST FANS
7) CONNECTIONS FOR COUPLINGS INSIDE A/C UNITS TO BE TIGHTENED
8) FILL UNUSED OPENINGS IN JUNCTION BOXES
9) 250.97 BOND BUSHING AT CONCENTRICS 250V OR HIGHER
10) SUPPORT BOXES IN CEILING
09/01/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) DO NOT BUNDLE M/C CABLES AND SUPPORT AS PER 334.30 2) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RINGS 314.20/370.20 METAL NOT APPROVED
3) ELECTRIC NOT FINISHED