Permit: T04CM03815

Parcel: 11449030A

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Date Description Inspector Results Comments
11/21/2005 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
08/28/2005 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) OK TO ENERGIZE PANELS A, B, X AND Y
2) MANUFACTURERS HOLDOWN TO BE EFFECTIVE
08/25/2005 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) FINISH MAKE UP AND DEVICES
2) WAITING ON HOLDOWN FOR MAIN
08/22/2005 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) PANEL "E" MANUFACTURES HOLD DOWN NEEDED
2) DEVICES 8' AND DOWN TO BE INSTALLED FOR PANELS TO BE ENERGIZED WITH INSPECTION
3) OK PANELS: E, A, B, Y, Z TO LUGS ONLY
08/18/2005 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) OK PANEL "Y" TO MAIN LUGS
2) OK TO TRANSFORMER T-1 TO LUGS
3) OK BONDING CT CAN AND "MDP"
4) VERIFY CONDUCTOR SIZE PANEL "Z"
5) PANEL "C" TO HAVE A MAIN BREAKER
6) PLANS CALL FOR CV GROUND EQUIPMENT CONDUCTORS
08/17/2005 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) OK TEMP POWER FOR TEST TO MAIN BREAKERS